One of the most important steps in the retrofitting process of a building is to understand its pre-retrofitting stage energy performance. The best choice for carrying this out is by means of a calibrated building energy simulation (BES) model. Then, the testing of different retrofitting solutions in the validated model allows for quantifying the improvements that may be obtained, in order to choose the most suitable solution. In this work, based on the available detailed building drawings, constructive details, building operational data and the data sets obtained on a minute basis (for a whole year) from a dedicated energy monitoring system, the calibration of an in-use office building energy model has been carried out. It has been possible to construct a detailed white box model based on Design Builder software. Then, comparing the model output for indoor air temperature, lighting consumption and heating consumption against the monitored data, some of the building envelope parameters and inner building inertia of the model were fine tuned to obtain fits fulfilling the ASHRAE criteria. Problems found during this fitting process and how they are solved are explained in detail. The model calibration is firstly performed on an hourly basis for a typical winter and summer week; then, the whole year results of the simulation are compared against the monitored data. The results show a good agreement for indoor temperature, lighting and heating consumption compared with the ASHRAE criteria for the mean bias error (MBE).
Except where otherwise noted, this item's license is described as 2021 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).