dc.description.abstractThe protection of high voltage direct current (HVDC) grids is a challenge considering that the protection system must detect, locate, and interrupt large fault currents in a few milliseconds. Resistive type superconducting fault current limiters (R-SFCL) can help solve that difficult task, reducing the extremely demanding ratings of HVDC circuit breakers. This paper presents different approaches to model R-SFCLs in order to analyze their suitability for assessing the performance of HVDC grid protection, including the step model, the exponential model, the RQ model, and the magneto-thermal model. In the first instance, the R-SFCL models are evaluated in a test grid to analyze their parameterisation and select the most adequate model for the study of HVDC grids. The RQ model is finally chosen for its simplicity but closer behavior to the magneto thermal model in terms of fault resistance dependency and resistance evolution curve. Then, the performance of an RQ type R-SFCL model in conjunction with a mechanical circuit breaker is evaluated in a multiterminal HVDC grid with different fault cases. This way, fault currents are greatly decreased as well as circuit breaker requirements. Hence, the R-SFCL under study enables a reliable protection of the HVDC grid.es_ES
dc.language.isoenges_ES
dc.publisherMDPIes_ES
dc.rightsinfo:eu-repo/semantics/openAccesses_ES
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/
dc.subjectHVDC grides_ES
dc.subjectfault current limiteres_ES
dc.subjectmodeles_ES
dc.subjectresistive typees_ES
dc.subjectsuperconductivityes_ES
dc.titleModelling of Resistive Type Superconducting Fault Current Limiter for HVDC Gridses_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.date.updated2022-07-08T11:55:30Z
dc.rights.holder© 2022 by the authors.Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/).es_ES
dc.relation.publisherversionhttps://www.mdpi.com/1996-1073/15/13/4605es_ES
dc.identifier.doi10.3390/en15134605
dc.departamentoesIngeniería Energética
dc.departamentoeuIngeniaritza elektrikoa


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record

© 2022 by the authors.Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/).
Except where otherwise noted, this item's license is described as © 2022 by the authors.Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/).