Show simple item record

dc.contributor.authorAraujo Parra, José Ángel ORCID
dc.contributor.authorLázaro Arrotegui, Jesús
dc.contributor.authorAstarloa Cuéllar, Armando Fermín
dc.contributor.authorZuloaga Izaguirre, Aitzol
dc.contributor.authorGárate Añibarro, José Ignacio
dc.date.accessioned2024-02-08T11:19:34Z
dc.date.available2024-02-08T11:19:34Z
dc.date.issued2015-01-21
dc.identifier.citationIEEE Transactions on Smart Grid 6(5) : 2325-2332 (2015)es_ES
dc.identifier.issn1949-3053
dc.identifier.issn1949-3061
dc.identifier.urihttp://hdl.handle.net/10810/65534
dc.description.abstractCritical systems require zero recovery time when a failure occurs in a communications network. The soon to be implemented standard IEC 62439-3 defines the only two protocols, parallel redundancy protocol and high-availability seamless redundancy, which fulfill this requirement and ensure no frame loss in the presence of an error. These protocols also provide a hot-plugging capability, which allows elements to be added to or removed from the network without interrupting communications and the operation of the plant. The electricity sector has adopted these for power utility automation in the recently published IEC 61850-90-4. The challenge is to obtain an efficient approach for use in electronic devices, capable of managing the characteristic duplicates, and circulating frames of these protocols, coupled with agile architectures capable of dealing with real-time processing requirements, fast switching times, high throughput, and deterministic behavior. The main contribution of this paper is the in-depth analysis it makes of network parameters imposed by the application of the protocols to power utility automation, and the proposition of a frame management system based on a segmented memory system that improves frame detecting time and uses the smallest memory required in order to resolve all the issues dealt with.es_ES
dc.description.sponsorshipResearch and Education Unit of the Department of Electronics Technology, University of the Basque Country (UPV/EHU) (Grant Number: UFI11/16) Department of Education, Universities and Research of the Basque Government within the fund for Research Groups of Basque University System (Grant Number: IT394-10)es_ES
dc.language.isoenges_ES
dc.publisherIEEEes_ES
dc.rightsinfo:eu-repo/semantics/openAccesses_ES
dc.subjectautomationes_ES
dc.subjectEthernet
dc.subjecthigh-availability
dc.subjecthigh availability seamless redundancy (HSR)
dc.subjectIEC 61850
dc.subjectIEC 62439-3
dc.subjectparallel redundancy protocol (PRP)
dc.subjectredundancy
dc.subjectsubstation
dc.subjectswitching
dc.titlePRP and HSR for High Availability Networks in Power Utility Automation: A Method for Redundant Frames Discardinges_ES
dc.typeinfo:eu-repo/semantics/articlees_ES
dc.rights.holder(c) 2015 IEEEes_ES
dc.relation.publisherversionhttps://ieeexplore.ieee.org/document/7017591
dc.identifier.doi/10.1109/TSG.2014.2387474
dc.departamentoesTecnología electrónicaes_ES
dc.departamentoeuTeknologia elektronikoaes_ES


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record